Yongliang2
(1. Guiyang Bureau, CSG EHV Power Transmission Company, Guiyang 550003, China;
2. CSG EHV Power Transmission Company, Guangzhou 510620, China)
Abstract: The cause of the event of electrode overvoltage protection (59EL) misoperation in Gaopo Converter Station of theGuizhou-Guangdong HVDC Transmission System, April 2, 2007, is analyzed, and a corresponding solution is given as follows: to setthe delay time of electrode overvoltage protection with 12 s, and to allow the HV bus switch to open when the DC station controlsoftware meets the original interlocked logic. The validity of the solution is proved by RTDS simulation.Key words: HVDC; electrode overvoltage protection; RTDS simulation
2007 年4 月2 日,高坡换流站极Ⅰ直流滤波器012LB 两套差动保护动作,极1 ESOF,极Ⅰ交流侧断路器跳开,中性母线断路器0010 跳开,随后极Ⅰ的3 套接地极过电压保护59EL 动作,站内高速接地断路器0040 合上,此时接地极电流几乎全部经站内接地网流过,导致极2 换流变压器存在直流分量,直流分量的注入引起了直流保护屏柜内I/V 变送器的饱和,极2 的3 套换流器角侧桥差保护Ⅱ段动作,极Ⅱ ESOF,同时极Ⅰ、极Ⅱ全部6 套站内接地网过流保护动作。
1 接地极动作原因分析
1.1 故障波形的分析针对2007 年4 月2 日高坡换流站极Ⅰ、极Ⅱ相继闭锁的事故,极2 跳闸根本的原因是极Ⅰ接地极过电压保护59EL 误动。分析极Ⅰ跳闸时刻的TFR波形,极Ⅰ中性母线电压绝对值最大达到了90 kV(59EL 的定值为75 kV),持续时间超过了100 ms,满足了59EL 保护动作判据。 信息来自:输配电设备网
1.2 RTDS 仿真试验分析
在南方电网技术研究中心仿真实验室,利用RTDS 与高肇直流实际的控制保护装置组成的闭环实验系统,仿真故障时刻极中性母线上电压值的大小,仿真结果如下: 信息来源:http://www.tede.cn
1) 肇庆换流站极Ⅰ在备用状态,极Ⅰ高压母线隔离开关05105 在合位,中性母线断路器0010在分位,极Ⅰ直流滤波器011LB 和012LB 均在连接状态,极Ⅱ在OLT 试验时,极Ⅰ高压母线和中性母线电压值如图1 所示。
2) 肇庆换流站极Ⅰ在备用状态,极Ⅰ高压母线隔离开关05105 在合位,中性母线断路器0010在分位,极Ⅰ直流滤波器011LB 和012LB 均在连接状态,极Ⅱ在正常运行时,极Ⅰ中性母线电压值如 信息来自:www.tede.cn
图2
从图1、图2 可以中清楚看出,极Ⅱ在OLT 试验和正常运行状态时,均能在停运极极Ⅰ直流线路上产生耦合压,最大值达到了136 kV,当停运极中性母线断路器在分位时,通过阀组RC 阻尼回路或直流滤波器反应在中性母线上的电压最大为105 kV,必然会导致接地极过电压保护的误动作。综上分析,接地极过电压保护误动的原因为正常运行极在停运极线路上产生耦合电压,同时反映在中性母线上的电压达到了接地极过电压保护的定值。
2 保护误动解决策略
来源: